For more information, refer to the RP-2002 & RP-2002E Manual, Document #53039. It is kept in the following location: Alarm Silencing. Notification Appliance Circuits may be silenced by pressing the ALARM SILENCE button. ALARM SILENCED will turn on yellow. Subsequent alarms will reactivate circuits. View & download of more than 160 Notifier PDF user manuals, service manuals, operating guides. Control Panel, Fire Alarms user manuals, operating guides & specifications. Notifier rp 2002 service manual, masculinities in british adventure fiction 1880 1915 author joseph a kestner published on march 2010, from neuron to brain 4th edition, sportline 345 user guide, google earth help manual, manual vw fox 2005, honda lawn mower repair manual hrt216, 5 out motion basketball, 1982 honda cb900f service manual, gilbert law.
DN-60444:B1 • 12/22/11 — Page 1 of 4
RP-2002C
Agent Release Control Panel
Conventional Releasing Panels
Canadian DN-60444:B1
General
The RP-2002C is a six-zone FACP for single and dual hazard
agent releasing applications. The RP-2002C provides reliable
fire detection, signaling and protection for commercial, indus-
trial and institutional buildings requiring agent-based releasing.
The RP-2002C is compatible with System Sensor’s i Talespin full episodes in hindi free download.
3
detec-
tors which are conventional smoke detectors that can transmit Coherence 5 2 3 – turn websites into apps without.
a maintenance trouble signal to the FACP indicating the need
for cleaning and a supervisory ‘freeze’ signal when the ambi-
ent temperature falls below the detector rating of approxi-
mately 7.22°C. In addition, the control panel is compatible with
conventional input devices such as two-wire smoke detectors,
four-wire smoke detectors, pull stations, waterflow devices,
tamper switches and other normally-open contact devices.
Refer to the Notifier Device Compatibility Document for a com-
plete listing of compatible devices.
Four outputs are programmable as NACs (Notification Appli-
ance Circuits) or releasing circuits. Three programmable
Form-C relays (factory programmed for Alarm, Trouble and
Supervisory) and 24 VDC special application resettable and
non-resettable power outputs are also included on the main
circuit board. The RP-2002C supervises all wiring, AC voltage,
battery charger and battery level.
Activation of a compatible smoke detector or any normally-
open fire alarm initiating device will activate audible and visual
signaling devices, illuminate an indicator, display alarm infor-
mation on the panel’s LCD, sound the piezo sounder at the
FACP, activate the FACP alarm relay and operate an optional
module used to notify a remote station or initiate an auxiliary
control function.
Features
• Listed to Standard ULC-S527-99.
• Designed for agent releasing standards NFPA 12, 12A, 12B,
and 2001.
• Meets International Building Code (IBC) seismic require-
ments.
• Disable/Enable control per input zone and output zone.
• Extensive transient protection.
• Dual hazard operation.
• Adjustable pre-discharge, discharge and waterflow delay
timers.
• Cross-zone (double-interlock) capability.
• Six programmable Style B (Class B) IDCs (Initiating Device
Circuit).
• System Sensor i
3
series detector compatible.
• Four programmable Style Y (Class B) output circuits - (spe-
cial application power).
• Strobe synchronization:
– System Sensor
– Wheelock
• Three programmable Form-C relays.
• 7.0 amps total 24 VDC output current.
• Resettable and non-resettable output power.
• Built-in Programmer.
• ANN-BUS for connection to optional devices (up to 8 total of
any of the following):
– N-ANN-80 Remote LCD Annunciator
– N-ANN-I/O LED Driver
– N-ANN-S/PG Printer Module (only one allowed per panel)
– N-ANN-RLY Relay Module
– N-ANN-LED Annunciator Module (built-in)
Barcode maker 2 12 download free. • 80-character LCD display (backlit).
• Real-time clock/calendar with daylight savings time control.
• History log with 256 event storage.
• Piezo sounder for alarm, trouble and supervisory.
• 24 volt operation.
• Low AC voltage sense.
• Outputs Programmable for:
– Releasing Circuits or NACS
• NACs programmable for:
– Silence Inhibit
– Auto-Silence
– Strobe Synchronization
– Selective Silence (horn-strobe mute)
– Temporal or Steady Signal
– Silenceable or Non-silenceable
– Release Stage Sounder
• Automatic battery charger with charger supervision.
• Optional Trim Ring TR-CE (red) for semi-flush mounting the
cabinet.
• Optional N-CAC-5X Class A Converter Module for Outputs
and IDCs.
• Optional 4XTM Municipal Box Transmitter Module.
• Optional Digital Alarm Communicators (411, 411UD,
Apple snipping tool shortcut. 411UDAC).
• Optional ANN-SEC card for a secondary ANN-BUS